Dielectric Fluid Filter
Used For: Dielectric Oil, Data Center and Crypto Mining Server Immersion Fluids (Mineral Oil, FR3, etc.), Load Tap Changer Oil, Transformer Oil
CAPACITY, SUMP SIZE & FLOW RATE
Requires 20 Qt./18.9 L. of makeup fluid (housing volume)
Oil sump range: 0-300 Gal./0-1135.6 L.
Flow rate range for transformer oil from 0-3 GPM/0-11.4 LPM
OVERALL DIMENSIONS
43” (H) Plus 20” Clearance above to remove filter
16.5” (W)
19” (D)
165 lbs./74.8 kg. shipping weight
SPECIFICATIONS
*3 GPM 65 PSI pump (not fluid flow rate) • 1/2 HP 1725 RPM washdown motor
120 volt, single phase
No power cord included
Pressure gauge NEW go-no-go gauge for indicating element • No hoses included
System fittings
Suction system end – 3/4” FNPT
Discharge system end – 1/2” FNPT
Max operating pressure 80 PSI
NOTES
**Flow rates are established using ISO 10-150 viscosity oils at the standard 40° C/104° F and are subject to vary
Viscosity, operating temperature, and generated contamination will affect sizing and flow rates of filtration equipment
Most applications, elements needs to be changed between 300-1000 hours for optimal performance, ideally change the element when the flow is half the starting flow or the PSI is double the starting PSI
Available in stainless-steel
Other system configurations are available
RECOMMENDED ELEMENT
Model 1004 for Dielectric Oil
Trinity Refining & Safety Systems is able to meet many custom requirements, please contact us with your specific custom needs.
MAGMICRON TECHNOLOGY
Charged polarity source + 1 micron filter element provides unequaled oil & fuel purification
Removes water and acid buildup
Extends engine life 3X
Reduces maintenance costs 85%
Reduces oil service 4X
Reduces engine rebuild by 67%
Reduces hydrocarbon emissions